UL 50 vs UL 508 enclosure | Information by Electrical Professionals …
Feb 2, 2016 · UL used the same nomenclature, and essentially the same requirements as NEMA did, effectively replacing them. As far as I know, a UL type enclosure meets all the NEMA requirements for the same type of enclosure, but is also listed, where as a NEMA type enclosure is not necessarily listed.
How to Select the Right Rubber Seal Material for UL 50E
Feb 22, 2016 · We have UL listed our compound 12BN7AP to the UL 50E. This is a 70 Shore A HNBR Black compound. This compound is also peroxide-cured to give great compression set resistance and temperature ranges from -40°C to +150°C. UL certified materials can be found on the UL online certification directory. End users can be assured the compounds used are ...
UL508A FLA Calculations Motor NP vs UL 50.1 Table
Jun 6, 2024 · If I have a few components, say two VFDs and a 3-phase to 24vdc PSU within an enclosure. The VFDs are connected to motors which have FLA's of 7.2A and 0.92A and the PSU's operating input current is 0.69A. The UL table 50.1 has the FLA's for the motors based on their HP at 7.6A and 1.1A respectively.
UL 508a transformer and power supply sizing | Information by …
Nov 25, 2024 · The max would be maybe 500W. I intend to use a 750VA transformer with 8A MEN fuse on the secondary, and 14AWG conductors on all secondary circuits. Would this meet UL 508A standards? Power supplies - 42.2.3 max 50% load unless it meets UL61010 etc. and then 42.2.3.2 sizing the overcurrent protection. This is all pretty clear that if the sum of ...
New Material For UL50 and UL50E - Hot Topics
May 16, 2013 · UL 50 and UL50E are the safety standards for Enclosures for Electrical Equipment, with and without environmental considerations. Some of the problems with selecting the correct gasket material for these applications are long term compression set, ozone and weather resistance, adhesion and crazing, and sulfur out gassing contamination.
UL 508a Certification Process - Mike Holt's Forum
Jul 25, 2021 · There is a whole 40 or 50 pages I think in the back of the UL standard it tells you how to calculate this. Most of it can be safely ignored if you know what to ignore, but getting your design in line with what u l will accept is not trivial in some cases.
UL508A, ICP's and Junction Boxes | Information by Electrical ...
Jun 9, 2023 · I have never experienced an AHJ consider a simple terminal box to be an ICP requiring a separate listing (the box itself must be UL-50 listed). Terminal and distribution blocks all by themselves are not considered part of the “component count” unless there is at least one other actionable component.
UL-50 Junction Box requirements | Information by Electrical ...
Apr 21, 2003 · Re: UL-50 Junction Box requirements Article 314 III Construction Specifications A talks about corrision resistant b talks about thickness of metal It says sheet steel boxes not over 100 cubic inches shall be made from steel not less than 1.59mm or.0625 in
I want to know the differences between NEMA and UL Standard.
Apr 19, 2016 · I want to know the differences between NEMA and UL Standard. One of our project's Client has specified that all electrical implement required to be BOTH to NEMA and UL Stanadards, these ontrol panel used in heavy industry, for UL stand ,i konow i should reference UL508A,but for nema stand what...
UL Listed Compounds - Hot Topics
Aug 22, 2013 · Apple Rubber listed its first UL compound back in July of 1986. After 27 years, we have increased our offering to 16 compounds with various end-use listing and polymer types. Now, Apple Rubber has a strong partnership with Underwriters Laboratories® (UL), and we work to provide safe products to our customers through UL testing, certification ...